Kirke Hyllinge Vandværk - Jenslev Vandværk
Region
Region Sjælland
Kommune
Lejre
Adresse
Nordre Ryevej 1
Indvindingsboringer
Vandværker
Ledningsnet
Forbrugers Taphane
Kontrolboringer
Forbrugers Taphane
| Parameter | Måling | Grænseværdi | Enhed | Dato | Forrige måling | |
|---|---|---|---|---|---|---|
| Fysisk - Kemisk | ||||||
| Hårdhed, total | 16,0 | grader dH | 09/07 2020 | 16,0 | ||
| Ammonium (NH4) | 0,010 | <= 0,050 | mg/l | 13/01 2020 | 0,013 | |
| Chlorid (Cl) | 18,0 | <= 250 | mg/l | 13/01 2020 | 19,0 | |
| Fluorid (F) | 0,430 | <= 1,50 | mg/l | 13/01 2020 | 0,460 | |
| Natrium (Na) | 28,0 | <= 175 | mg/l | 13/01 2020 | 27,0 | |
| Nitrat (NO3) | 4,70 | <= 50,0 | mg/l | 13/01 2020 | 5,10 | |
| Nitrit (NO2) | 0,053 | <= 0,100 | mg/l | 13/01 2020 | 0,001 | |
| Sulfat (SO4) | 5,90 | <= 250 | mg/l | 13/01 2020 | 5,40 | |
| Kosmetiske | ||||||
| Jern (Fe) | < 0,010 | <= 0,200 | mg/l | 24/06 2021 | < 0,010 | |
| Mangan (Mn) | < 0,002 | <= 0,050 | mg/l | 13/01 2020 | < 0,002 | |
| Mikrobiologiske | ||||||
| Coliforme bakt.37Gr. | < 1,00 | < 1,00 | MPN/100 ml | 24/06 2021 | < 1,00 | |
| E.coli | < 1,00 | < 1,00 | MPN/100 ml | 24/06 2021 | < 1,00 | |
| Enterokokker | < 1,00 | < 1,00 | CFU/100 ml | 13/01 2020 | < 1,00 | |
| Kimtal 22Gr. | 2,00 | < 200 | antal/ml | 24/06 2021 | 15,0 | |
| Uorganiske sporstoffer | ||||||
| Nikkel (Ni) | < 0,030 | <= 20,0 | µg/l | 13/01 2020 | < 0,030 | |