Stamdata

Region
Region Midtjylland
Kommune
Struer
Adresse
Kongevejen 48, Jegindø , 7790 Thyholm
Kontaktperson
Calle Schmidt
Telefon
2536 9795
Hjemmeside

Forbrugerinformation

Analyser ved afgang vandværk

Parameter Måling Grænseværdi Enhed Dato Forrige måling
Fysisk - Kemisk
Ammonium (NH4) < 0,020 <= 0,050 mg/l 14/06 2023 < 0,020
Chlorid (Cl) 44,0 <= 250 mg/l 22/07 2021 44,0
Fluorid (F) < 0,050 <= 1,50 mg/l 22/07 2021 0,100
Hårdhed, total 14,9 grader dH 14/06 2023 13,7
Kalium 1,70 mg/l 29/03 2017 1,80
Natrium (Na) 26,8 <= 175 mg/l 22/07 2021 27,6
Nitrat (NO3) 30,0 <= 50,0 mg/l 14/06 2023 26,0
Nitrit (NO2) < 0,001 <= 0,100 mg/l 14/06 2023 < 0,001
Oxygen/Iltindhold 7,10 mg/l 14/06 2023 7,70
Sulfat (SO4) 48,0 <= 250 mg/l 22/07 2021 47,0
Kosmetiske
Jern (Fe) < 0,002 <= 0,200 mg/l 14/06 2023 0,007
Mangan (Mn) < 0,001 <= 0,050 mg/l 14/06 2023 < 0,001
Mikrobiologiske
Coliforme bakt.37Gr. < 1,00 < 1,00 MPN/100 ml 14/06 2023 < 1,00
E.coli < 1,00 < 1,00 MPN/100 ml 14/06 2023 < 1,00
Enterokokker < 1,00 < 1,00 CFU/100 ml 14/06 2023 < 1,00
Kimtal 22Gr. < 1,00 < 200 antal/ml 14/06 2023 < 1,00
Kimtal 37 grader < 1,00 antal/ml 31/10 2017 < 1,00
Uorganiske sporstoffer
Nikkel (Ni) 0,510 <= 20,0 µg/l 14/06 2023 0,540

Analyser på ledningsnettet

Parameter Måling Grænseværdi Enhed Dato Forrige måling
Fysisk - Kemisk
Ammonium (NH4) 0,003 <= 0,050 mg/l 03/02 1998 < 0,003
Chlorid (Cl) 47,0 <= 250 mg/l 03/02 1998 48,0
Fluorid (F) 0,140 <= 1,50 mg/l 03/02 1998 0,140
Hårdhed, total 14,0 grader dH 03/02 1998 14,0
Kalium 1,60 mg/l 03/02 1998 1,80
Natrium (Na) 31,0 <= 175 mg/l 03/02 1998 32,0
Nitrat (NO3) 34,0 <= 50,0 mg/l 03/02 1998 33,0
Nitrit (NO2) 0,016 <= 0,100 mg/l 08/11 2023 < 0,001
Oxygen/Iltindhold 8,80 mg/l 20/11 2018 8,80
Sulfat (SO4) 51,0 <= 250 mg/l 03/02 1998 54,0
Kosmetiske
Jern (Fe) 0,004 <= 0,200 mg/l 14/03 2022 < 0,002
Mangan (Mn) < 0,020 <= 0,050 mg/l 03/02 1998 < 0,020
Mikrobiologiske
Coliforme bakt.37Gr. < 1,00 < 1,00 MPN/100 ml 08/11 2023 < 1,00
E.coli < 1,00 < 1,00 MPN/100 ml 08/11 2023 < 1,00
Enterokokker < 1,00 < 1,00 CFU/100 ml 08/11 2023 < 1,00
Kimtal 22Gr. < 1,00 < 200 antal/ml 08/11 2023 2,00
Kimtal 37 grader 3,00 antal/ml 08/09 2004
Uorganiske sporstoffer
Nikkel (Ni) 0,300 <= 20,0 µg/l 08/11 2023 0,490
Analyser
Seneste analyser
Seneste analyse er indrapporteret 30/01-2024.
Overskridelser
Ingen fundet
Stamdata
Region
Region Midtjylland
Kommune
Struer
Adresse
Kongevejen 48, Jegindø , 7790 Thyholm
Kontaktperson
Calle Schmidt
Telefon
2536 9795
Hjemmeside


mitdrikkevand.dk

Mitdrikkevand.dk er et tilbud til alle typer vandværker og forsyninger samt industri/landbrug/dambrug, som ønsker sig et aktuelt og hurtigt overblik over anlæggets og grundvand/drikkevandets tilstand og udvikling. Læs mere på menuen kontakt og information eller ring til DVN på 98 66 66 66